XM3.1-915-HP
Power Supply
Alarms
Battery
Log In...
English
Español
Français
Português
Deutsch
Overview
Hardware
Power Supply
Batteries
Environmental I/O
Components
Network
DOCSIS
RF Attenuation
Ethernet
Advanced
Interfaces
Network Services
Diagnostics
Management
System Data
SNMP
Alarms
Utility Power
History
Power Supply Events
Power Supply Configuration
Battery Events
Standby Events
Modem Log
Network System Log
Network Event Log
Firewall Log
Alarm Log
Tools
Spectrum
Microreflections
d
Power Supply
Model
ALPHA/XM3.1-915-HP
Firmware
V1.01.0
Major Alarm
OK
Minor Alarm
OK
Operational Mode
Line
Charger Mode
Rest
Tamper
Closed
Power Supply Language
English
Power Supply Priority
Normal
d
Input
AC Line Mode
OK
Voltage
122.43
V
Current
5.05
A
Power
539
W
Frequency
60
Hz
Tap Status
Normal
Frequency Range
3.00
Hz
Current Limit
17.00
A
Input Power Consumption
2,142
Wh
1
Output
Voltage
61.98
V
Power
425
W
Apparent Power
477.86
VA
Frequency
60.05
Hz
Percent Load
51.20
%
Output Setting
60 V
Output Regulation
Fine
Over-current Tolerance
3.000
sec
Retry Delay
60
sec
Retry Limit
20
Active Drop Alarm
OK
Active Drop Threshold
50
W
Current
7.71
A
d
Inverter
Inverter Status
Off
End of Discharge Type
String
End of Discharge Level
1.75
V/cell
Reduced Peak Mode
Disable
Total Standby Events
93
Time Since Last Standby Event
32d 16h:39m
Time in Last Standby Event
0d 0h:01m
Total Time in Standby
792
min
Standby Events Since Reset
42
Time in Standby Since Reset
355
min
Time Since Reset
1,269
day(s)
Total Run Time
1,269
day(s)
Transformer Run Time
1,269
day(s)
Total Downtime
0d 0h:23m
Oil Cap Lifespan Consumed
32.1
%
d
Self Test
Deep Discharge Cycle
Timed
Test Countdown
1
day(s)
Test Duration
10
min
Test Interval
30
day(s)
Test Inhibit
No
→ CSV
→ Excel
Copyright © 2021 Alpha Technologies Services, Inc. - an EnerSys company
www.alpha.com
|
www.enersys.com
Close